24
|
55.1.5 As per item 1.1, but EI90, height approx. 2.35 m (PV5); without acoustic requirements [ml] Installation [...]
|
|
24/01/2017
|
|
22
|
Could you elaborate on the concept of "valeur hors terrain et hors sol du projet " in document " PE_- [...]
|
It refers to the overall cost of the aboveground part of the project (without subsoil) and without the [...]
|
19/01/2017
|
|
23
|
Following your reply to question 22, we have interpreted that the " montant des travaux réellement exécutés [...]
|
The " montant des travaux réellement exécutés par le soumissionnaire '' refers to the part of the value [...]
|
19/01/2017
|
|
21
|
Hello. Are the documents referred to in points 13.1 to 13.3 to be supplied with the tender, or are they [...]
|
1) In accordance with point 13.7 of the Specifications, ‘... the European Parliament accepts the declaration [...]
|
03/01/2017
|
|
20
|
Hello. Can you provide us with an area in which to unload lorries close to the goods lifts? Will the [...]
|
No, there will not necessarily be an unloading area next to the goods lifts. Horizontal transfer from [...]
|
03/01/2017
|
|
19
|
55.1.6 Melamine coating for the partitioning The description states that the cladding should be approximately [...]
|
For the section of frame above the door, the panel height must be roughly 42 cm, elsewhere the panels [...]
|
03/01/2017
|
|
18
|
1.8. Door components (7.) Climatic classification for wooden doors Minimum requirement to be met/evidenced [...]
|
Confirmation: Climatic classification 2b in accordance with DIN EN 12219 for wooden doors.
|
03/01/2017
|
|
16
|
1.8.(2.) Wooden door The description makes a distinction in thickness between the door leaves according [...]
|
Tenderers must indicate in the tender what thickness of door panel they consider necessary to achieve [...]
|
03/01/2017
|
|
15
|
1.8.(2.) Wooden door Contradiction between the thickness mentioned in this article and detailed plan [...]
|
Tenderers must indicate in the tender what thickness of door panel they consider necessary to achieve [...]
|
03/01/2017
|
|
14
|
1.8.(2.) Wooden door Composition of the door leaf: Lacquered finish contradicts the description in the [...]
|
The doors must be glazed.
|
03/01/2017
|
|
13
|
1.6.7. Definition of colours Can you explain: (2.) Light-reflection index between partition door frame [...]
|
(2.) Tactile contrast definition = luminance contrast: >= 30 LRV. It is a difference in brightness [...]
|
03/01/2017
|
|
12
|
1.4. Physical building constraints 1.4.4. Fire stability The description of the fire resistance classification [...]
|
All wall and emergency escape compartment coverings must have a fire resistance rating of at least Euroclass [...]
|
03/01/2017
|
|
11
|
1.4. Physical building constraints 1.4.4. Fire stability The fire resistance of the various removable [...]
|
Firewalls are to be provided in the positions shown under items description CA14.
|
03/01/2017
|
|
10
|
1.2.2. Overall description / door (4.) List of doors the text refers to documents KAD____-06TPP_____- [...]
|
The document referred to is not part of the file. Reason: the doors are equipped only with a handle, [...]
|
03/01/2017
|
|
9
|
Part E. Supporting documents necessary for the verification of compliance with the selection criteria [...]
|
1) The model PE_-160321-CA_-Economic_viability.xlsx has been replaced by model PE__-160525-CA__-Turnover_Operating [...]
|
03/01/2017
|
|
8
|
1. How is the delivery of the removable partitioning organised? Are there goods lifts to transport them [...]
|
1. See reply to the question of 14.12.2016; 17.46. 2. For chapter 1 of CA14, the cost of the doors is [...]
|
03/01/2017
|
|
7
|
What percentage deductions should be made in calculating proportional charges such as for electricity [...]
|
Works management costs are reimbursed by the European Parliament, including for lot 2, logistics, waste [...]
|
03/01/2017
|
|
6
|
Question 8: The total wall loading is given here as 500kg/m on both sides. Is the specification with [...]
|
Loads should comply with the DIN 4103-1 standard (in relation to DIN 18183-1) for installation zone 2 [...]
|
03/01/2017
|
|
5
|
Question 7: What difference in pressure [Pa] should there be between corridor and office?
|
The maximum head loss between corridor and office is 25 Pa.
|
03/01/2017
|
|
4
|
According to the CTPG general and special technical specifications p.16, 1.4.4 ‘Stability on exposure [...]
|
4. All wall and emergency escape compartment coverings must have a fire resistance rating of at least [...]
|
03/01/2017
|
|
3
|
Question 1: Could a coated wooden door of the same surface quality as the wall plate be offered in place [...]
|
1. Variants are not permitted. 2. Variants are not permitted. 3. Variants are not permitted.
|
03/01/2017
|
|
2
|
Dear, Is it possible submit a tender without the full dossier (expired on 24th November)? which kind [...]
|
Tenders may be submitted until 25 January 2017. As indicated in section VI. 3. of the contract notice [...]
|
03/01/2017
|
|
1
|
Dear Sir/Madam, my questions concern the request for ‘one (1) reference in respect of a new non-residential [...]
|
1) Yes, supplies may have been delivered in batches, but for the same new tertiary building project completed [...]
|
03/01/2017
|
|
17
|
1.8.(3.) Frame Contradiction between the description of an aluminium frame and detailed plan KAD____- [...]
|
Intended as block-frame. Hereto see additionally plan attached (KAD____-07ACL002_____-TB01-692-EXE-CA-BPE [...]
|
22/12/2016
|
|