27
In Lot 1, Lot 2, Lot 3 - Work Hours Can you please confirm if the hourly rate is per person or for a [...]
The hourly rates are per person.
20/11/2019
21
Please advice the part numbers and reference order codes for the following equipment: 1. Fire Pumps 2 [...]
In addition to what previously replied, for all lots, the equipment/system must be compliant with British [...]
20/11/2019
26
1. Please specify whether the lift reader is within the lift cabin. 2. The relay interface board for [...]
1. The lift reader is inside the lift cabin. 2. The lift travels for 5 floors (from – 1 to 3). Floor [...]
15/11/2019
25
1. As per clarification note 2, Easo currently has 8 channel and 16 channel NVRS. Please confirm that [...]
1. We Confirm that the item 3.01.04 have to cater for an 8 channel NVR and the item 3.01.07 we have to [...]
15/11/2019
24
Please advice the power of electrical pump The replacement of pump impeller and pump motor are very specialized [...]
Question14 See point 2.
15/11/2019
23
Please advice the manufacturer name of the cylinders and the actuators for the Argonite suppression system [...]
Both are GINGER-KERR Manufactured by Kidde Products. Please refer to the labels that are provide in the [...]
15/11/2019
22
Please advise the drill size of the discharge nozzle which has been requested for the suppression systems [...]
The drill size is 7 mm.
15/11/2019
20
Please specify the following information so that we can continue our correspondence with our suppliers [...]
Question14Question17
15/11/2019
19
We would greatly appreciate receiving further information regarding the intercom system as without the [...]
Question16
15/11/2019
18
Please advice the model, manufacturer of the VESDA panel.
The panel is VESDA LaserPLUS. No brand was indicated as equivalent systems can be provided by the tenders [...]
15/11/2019
17
Please specify the sizes of the strainers (bill item 1.01.03), check valve (1.01.04) and isolation valve [...]
The size is 100 mm.
15/11/2019
16
Please advice the manufacturer, model of the external and internal video intercom units.
The current units are Urmet and Aiphone JB-DV. No brand was indicated as equivalent systems can be provided [...]
15/11/2019
15
Please specify the models, manufacturer of the current NVRS which would need to be replaced so that we [...]
Manufacture and Model: HIK – DS- 7716N1-14/16P. Please note that a different equivalent model and brand [...]
15/11/2019
14
1. Please specify the type of existing pump installed i.e. whether the existing pump is end suction, [...]
1. The existing pump is a Vertical turbine. 2. 37 Kw/7 Bar. Please refer to the labels that are provide [...]
15/11/2019
13
Reference is made to the reply to question 7. Can you please confirm that an extension will be granted [...]
Any reference to the deadline extension will be communicated in the next days by a publication of a Contract [...]
14/11/2019
12
We kindly request an extension to the tender deadline.
Question7
13/11/2019
11
Please advice the manufacturer, make, model of the hose reel. Kindly note that the most cost effective [...]
Like all the other spare parts, EASO will assess the technical options available in case of breakdown [...]
13/11/2019
10
Kindly advice if the existing fire pump set is electrically driven or electrical and diesel.
The existing fire pump is electrically driven.
13/11/2019
9
With reference to item 3.01.07. Please confirm that the workstation being requested is an NVR required [...]
The workstation is an NVR.
13/11/2019
8
With reference to 3.01.07 which readers workstation for 16 cameras: please confirm that an NVR for 16 [...]
An NVR is requested
13/11/2019
7
We kindly request an extension to the tender deadline by at least a week.
Please note that a Contract notice corrigendum will be published in this sense
13/11/2019
6
Please advice the pressure of the gas cylinders for the suppression system whether they are 200 bar or [...]
They are 200 bar
13/11/2019
5
With reference to bill item 1.05.08 having quantity 12, please confirm that this is referring to 12 cylinders [...]
Yes it refers to 12 cylinders
13/11/2019
4
1. Please advice the manufacturer of the existing suppression system and also model. 2. Kindly advice [...]
1. EASO has one FM 200 suppression system and five ARGONITE suppression systems. ECP panels are Prescient [...]
13/11/2019
3
Please advice the manufacturer, model no, brand and protocol of the existing fire alarm and detection [...]
It is Advanced, X 5 Pro
13/11/2019