Call for tenders' details

Title:
DIGIT/R3/PO/2016/020 - Data centre compute solutions (DCCS).
Contracting authority:
European Commission, DG Informatics (DIGIT)
TED publication date:
28/02/2017
Time limit for receipt of tenders:
24/04/2017
Status:
Closed
Show filter parameters

Results per page: 10 | 25 | 50 157 Questions found, displaying 1 to 10.[First/Prev] 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 [Next/Last]
# Question Answer Last publication date Status
1
On the initiative of the European Commission, tenderers are advised that Annex 3 to the Tendering Specifications [...]
For Lot 1, Annex 3 to the Tendering Specifications is modified, as follows: 1- Configuration 2 sockets [...]
08/03/2017
2
The last paragraph of this section says : "The signatory states that the person …..the documentary evidence [...]
a) References to earlier procedures can be made as follows: Under "Document": e.g. "Social security certificate [...]
15/03/2017
3
a) Do bidders have to be compatible with the existing UPS, (if yes ; which Brand & type) ? b) Or [...]
The 'Annex 3 to TS – Minimum Technical Requirements' document has been amended regarding the 'Power' [...]
15/03/2017
4
Common criteria: -The proposed configurations must contain all necessary softwares and licenses to allow [...]
a- The required software and licenses to enable the integration of the proposed server with the 3 products [...]
15/03/2017
5
Blade: -network connectivity: Some features like SRIOV are only available on 1/10Gb Nics, and may only [...]
a- The mandatory minimum technical requirements for the blade network interface and the enclosure's switch [...]
15/03/2017
6
All systems: System for communication with the UPS and automatic shut-down / restart. Which type of UPS [...]
a- See Answer N° 3: the 'Annex 3 to TS – Minimum Technical Requirements' document has been amended regarding [...]
15/03/2017
7
2 sockets standard: -Storage bays: Proposed configuration must support at least 24 2.5" SAS disks. "Proposed [...]
a-The hardware for the additional disks is the Raid Controller, the cage, back-plane and internal cabling [...]
15/03/2017
8
4 sockets Standard + Advanced: -In the 4S standard config a form factor of max 4U is requested, in the [...]
a-The form factor must be 4U. The 'Annex 3 to TS – Minimum mandatory requirements' has been updated to [...]
15/03/2017
9
-The proposed configurations must contain all necessary softwares and licenses to allow full integration [...]
a- See answer N°4 a: the required software and licenses to enable the integration of the proposed server [...]
15/03/2017
10
Blade: -network connectivity: Some features like SRIOV, VXlan are only available on 1/10Gb Nics, and [...]
a- See answer N° 5 a: the mandatory minimum technical requirements for the blade network interface and [...]
15/03/2017