170
With regard to file “EN-03-Financial offer form_001“ please note that for some items is difficult to [...]
No manipulation of the excel files to be filled in for the financial and the technical offers is allowed [...]
24/07/2020
Answered
169
Please clarify if at the end of the 4 years O&M period, on the engine must be done the major overhaul [...]
The Contractor has to perform the maintenance of the engines according to the maintenance requirements [...]
24/07/2020
Answered
168
In the contract art. I.14.9 is indicated “ In the event of failure by the Contractor to carry out the [...]
The intervention will be defined as "urgent" at the moment of the request. The delay will be evaluated [...]
24/07/2020
Answered
167
With regard to answer clarification N 122 , with refer to the following text “… “The cost related to [...]
At the moment this information is not available as the annual fee for maintenance covers the existing [...]
24/07/2020
Answered
166
With regard to the signature of the “Annex 5.3 —Financial and Economic Capacity Overview Form” in which [...]
The “Annex 5.3 —Financial and Economic Capacity Overview Form” should only be signed by the Chief Accounting [...]
24/07/2020
Answered
165
According to EN-03-Financial offer firm, following earthing grid material should be quoted: - 63mm2 copper [...]
The indicated sections are typical for reference, tender alignment purposes. The earthing material shall [...]
24/07/2020
Answered
164
Referring to the sheet "Breakdown of works and supplies" of the document "EN-03-Financial offer form_ [...]
The tenderer is invited to express prices for which a supply and a manpower, splitting the two parts [...]
24/07/2020
Answered
163
According to EN-03-Financial offer firm, two items 2.4.1.5 (supply and erection of PCC LV Switchboard [...]
Existing QE-TEC2 shall not be replaced in this project, only feeder in new QGBT-59A has to be envisaged [...]
24/07/2020
Answered
162
According to EN-03-Financial offer firm, item 2.4.3.4 (FG16R16 0.6/1kV - 1x240 / 1x185) should be quoted [...]
All cable sections indicated are preliminary and must be calculated by contractor based on the actual [...]
24/07/2020
Answered
161
We ask you to confirm that the performance guarantee as the letter for performance first demand guarantee [...]
We hereby confirm the provisions of the contract under Article I.6.1.1: The guarantee must be issued [...]
21/07/2020
Answered