52
|
In the document "DRAFT SUPPLY AND MAINTENANCE CONTRACT" at page 17 in the article "ARTICLE II.11 – LIQUIDATED[...]
|
"V" is the amount specified in Article I.3.1, for each stage. Please consider also the answer to the [...]
|
28/09/2015
|
|
50
|
Please confirm that the route of the cable already exists, and if so, can you indicate the path? Do you[...]
|
In respect to the DC cable that connects the outdoor unit with the indoor unit we will indicate the path[...]
|
24/09/2015
|
|
38
|
On page 4 of the technical specifications, it indicates that the system must permit a "smooth" and automatic[...]
|
An electromechanical switch is allowed as there is no negative impact for the technical requirements.
|
14/09/2015
|
|
53
|
In the document "DRAFT SUPPLY AND MAINTENANCE CONTRACT" at page 21 in the article“II.14.5 Pre-financing[...]
|
Please refer to the article I.4 of the draft contract where it is not requested to provide a financial[...]
|
28/09/2015
|
|
22
|
In the document “technical specification” on page 10 section 4 paragraph 1, it specifies that the delivery[...]
|
For both lots: Following a review of the technical specifications, we inform you that the delivery time[...]
|
09/09/2015
|
|
6
|
Question 1: In respect to the documents to be provided by the tenderer, including by the “sub-contractor[...]
|
1. Subcontractors shall submit the same documents as the main contractor; the document in copy for the[...]
|
07/09/2015
|
|
7
|
Question: In the document “Technical specifications” on page 8, third point, it refers to a range between[...]
|
The unit of measurement is VAR and not VOLTS. The correct values are -60kVAR < Q < +60kVAR for [...]
|
07/09/2015
|
|
8
|
Question: In the document “Technical Specifications” on page 8, point 7th, it is defined a complete cycle[...]
|
For the lot 1 the correct value is 150 KWh and not 1 MWh. For the lot 2 the correct value is 450 KWh [...]
|
07/09/2015
|
|
9
|
Question: In the document “Technical Specifications” on page 8, point 8th, Is the word ‘... 1 MWh capacity[...]
|
The maximum capacity for the lot 1 is 150 kWh and for lot 2 is 450 kWh. The complete cycle per day (24[...]
|
07/09/2015
|
|
37
|
On page 4 of the technical specifications, it indicates that the system should permit a "smooth" and [...]
|
The system can be operated in 3 different modes (see requirements A4, A5, A6, B1, B9, C1, C5, C10 and[...]
|
14/09/2015
|
|