Question details
Questions according tender NEAR/TGD/2022/EA-OP/0142
Question 5 Considering dimensions of the container it is said that is should be 20ft(witch is pprox. 6m) in length with the cooling units on the side wall,but it is also said that inside room dimensions should be approximately 2.6m x 2.8m x 5.7m witch leaves only 0.3m for the cooling units on the side wall.So if the side wall is considered to be outside of the room it is physically impossible to insert a cooling unit in just 0.3m to fulfill the requirement. So my question is if the side wall can be considered individually or it must be included in these dimensions? Question 6 In specification for racks it is said that server rack dimensions are 1000/1060mm but without doors. Is it possible to have 1000/1100mm dimensions that include doors in its specification? Because it is very difficult to find a vendor that describes in detail how much rack dimensions would be without the doors, because every vendor includes them in its dimensions. Question 7 Does power generator need to come along with mobile data center or it is considered to be found individually? Usually vendors do not offer power generator with mobile data centrists it needs to be found individually.